A Hybrid Edge-AI Framework for Proactive Indoor Air
Quality Management: Integrating LSTM-Based
Prediction with Multi-Criteria Risk Mitigation
Moinuddin Khan,
*
Sadeem Khan, Saloni Kadam, Alfiya Ansari, Abdul Arham Malik, Amol Sankpal and Feroz Shaikh
Department of Computer Engineering, Anjuman-I-Islam M. H. Saboo Siddik College of Engineering, Mumbai, Maharashtra, 400008,
India
*Email: moinuddin.241624.et@mhssce.ac.in (Moinuddin Khan)
Abstract
Conventional smart-home purifiers function as passive filtration units, often lacking mechanisms to mitigate
secondary hazards like airflow-driven fire propagation. This research proposes an autonomous, vision-aware
Edge-AI safety framework that integrates real-time air quality forecasting, predictive maintenance, and active
hazard mitigation into a unified embedded architecture. A localized LSTM network performs AQI forecasting
with a mean absolute percentage error (MAPE) of 5.8%, with 32ms inference latency. To enhance reliability, the
framework introduces offline voice intelligence (VC-02) for internet-independent reporting and a multi-axial
vision layer for redundant fire verification, neutralizing false-positive triggers. Physical validation was
conducted using 4 real fire and non-fire sources and one non fire source (orange coloured cloth) confirming
that the system operates reliably under realistic residential conditions. To assess the challenge of the conflict
that arises between air circulation and the accelerating combustion process, the forecasting engine was tested
on a real-life indoor environmental dataset acquired from the publicly available DALTON repository. Tested on
the novel test sequences, the quantized on-device LSTM model reached a level of RMSE of 3.12 IAQ units and a
level of MAPE of 5.8%, demonstrating a high accuracy of the model in practical applications, indicating strong
mathematical feasibility for real-time applications. The system employs high-priority hardware interrupts
linked to an active multi-directional suppression mechanism. Experimental results confirm a deterministic
response, achieving an 87ms latency for relay deactivation and pump-based intervention. Bench-marking
against industry leaders indicates superior safety responsiveness, transitioning the device from a passive
cleaner to an active safety robot. This work directly addresses the United Nations SDG-3 (Good Health) and SDG-
11 (Sustainable Cities) objectives by providing autonomous safety infrastructure for high-density urban
residential environment.
Keywords: Edge-AI; Indoor air quality; LSTM, Fire mitigation; Offline voice intelligence; Multi-axial vision verification;
Predictive maintenance.
1. Introduction
1.1 Indoor air quality
Epidemiological data suggests that a significant percentage of a global population is consistently exposed to
indoor air pollutants. A WHO survey found about 90% of people live in areas where pollution exceeds safety
guidelines.
[1]
Chronic exposure to indoor pollutants, including fine particulate matter and gaseous compounds,
has been associated with a broad spectrum of adverse health outcomes, encompassing cardiopulmonary
disease, several cancers, diabetes mellitus, and dementia.
[2]
In high density urban environment like Mumbai, where living spaces are often as congested. In such settings,
indoor air quality can quickly deteriorate because limited ventilation, daily cooking and outdoor traffic
emissions all combine to increase pollutant levels. Over time, the number of hours spent breathing this impure
air accumulates and may lead to serious long-term health effects for the occupants. Indoor Air Quality (IAQ) is
affected by several parameters such as temperature, relative humidity, CO, CO
2
, formaldehyde (HCHO), total
volatile organic compound (TVOC) and particulate matter (PM2.5, PM10).
[3]
Air pollution, including particulate
matter (PM) of various size fractions, is known to cause various adverse health effects. Exposure to PM with an
aerodynamic diameter of ≤ 2.5 µm (PM2.5) has been associated with chronic obstructive pulmonary disease
(COPD), acute and chronic cardiovascular disease, several cancers, diabetes mellitus, and dementia.
[4-6]
Beyond passive monitoring, there is a growing demand for interactive systems where user can query health
diagnostics through offline voice commands, ensuring accessibility even for non-technical users.
1.2 Conventional air purifiers
Conventional air purifiers typically combine HEPA filters for removing fine particulate matter with activated
carbon filters for reducing gaseous pollutants and odors. Advanced models may cost more than INR 40,000,
creating a potential socioeconomic barrier to adoption among low- and middle-income households. However,
the operation of many conventional purifiers remains relatively basic. Users generally select a fan speed or
activate an automatic mode, while the purifier adjusts its operation according to limited sensor inputs rather
than comprehensively interpreting the changing indoor environment. Some advanced models incorporate
particulate-matter or gas sensors to regulate fan speed based on predefined thresholds. Nevertheless, these
systems may remain expensive and often rely on threshold-based control mechanisms to monitor indoor air-
quality variations over time.
[7]
Consequently, conventional purifiers may not respond adequately to sudden changes in indoor pollution levels
caused by activities such as intensive cooking,
[8]
the use of strong cleaning chemicals, or the infiltration of
outdoor smog. In extreme situations, such as fires or severe smoke events, increasing the fan speed to improve
air filtration may not necessarily enhance safety and could potentially contribute to the circulation of smoke
and air within the affected space. Therefore, conventional air purifiers may lack the integrated safety logic
required to distinguish routine pollution events from potentially hazardous conditions.
[9]
1.3 Limitations of conventional air purifiers in fire scenarios
Mainly designed with one goal in mind that is to remove dust, smoke and smells so that a room feels cleaner and
more comfortable to breathe in. They do this by pulling air through filters and pushing the cleaned air back into
the room using a fan. In normal situations, this behaviour is useful and helps to reduce day-to-day exposure to
indoor pollutants. Conventional consumer air purifiers typically have limited alerting systems that rely on coded
sounds like chirps (constant sounds for bad air quality or quick beeping for moderate quality) and the display
of air quality on a screen. Audio data have proven to be ambiguous in terms of their meaning when it comes to
simple functionality tests, especially when the user has not read the manual. Moreover, the lack of reports in
natural language adds difficulty to the operation, especially for younger and elderly operators dealing with the
alerts, because they have coded beep pattern (Ex: Short Beep for moderate AQI, long 3 times beep for Poor AQI)
and only a single page interface where IAQ level is shown, they do not have any alerts if the filter needs to be
changed its all-time based, they don’t give any voice alerts which can be understand by everyone. There is a
usability barrier for non-technical users and elderly.
The problem starts when we look at what happens during a fire or a severe smoke event. Most consumer
purifiers cannot actually understand that there is a fire; they only sense that the air is very smoky and then
increase the fan speed to try and clean it faster. In a closed room, this stronger airflow can unintentionally keep
feeding fresh oxygen towards the flames and help the fire to grow or spread more quickly instead of slowing it
down and existing solution lack integration of multi-modal safety protocols leaving a critical gap in proactive
hazard mitigation. In other words, the same device that improves comfort in normal conditions can become
risky in an emergency because it has no built-in safety logic to shut itself down or change its behaviour when
fire is present.
1.4 Need for the proposed system
The proposed hybrid Edge-AI system combines multiple sensors, a local prediction model and fast hardware
control on the same embedded board.
[7]
By running the AI model directly on an edge device like an ESP32, the
purifier can observe trends in PM₂.₅ and gas levels, voice command base status of Air Quality, Filter health,
Temperature and can warn users earlier with real time voice alerts in any language , and immediately shut down
the fan and trigger alarms when it detects conditions that look like a fire or a hazardous event, and in case of
fire, the suppression system get active and suppress the fire with 2 step verification from sensor and camera
(vision-verification) without depending on any cloud connection.
[7,10]
Three critical capabilities have been introduced in the proposed system: (1) Offline Voice Intelligence, which
utilizes the VC-02 module to provide internet-independent voice feedback and enable users to query air-quality
status and filter health during network outages; (2) Vision-Assisted Monitoring, which integrates a multi-axis
camera–servo assembly to support visual verification of potential fire events and monitoring of window states,
with the intended aim of reducing false-positive alarms; and (3) Active Hazard Mitigation, which employs a
dual-pump actuation mechanism for localized fire-suppression actions based on real-time inputs from a five-
channel flame-sensor array. The primary contribution of this research lies in system-level hardware–software
integration and edge co-design rather than the development of a novel neural-network architecture. The
integration of a quantized LSTM-based time-series predictor with deterministic hardware-interrupt safety
procedures on a dual-core microcontroller is intended to support rapid hazard response while maintaining
efficient power and memory usage. Experimental evaluation yielded a MAPE of 5.8% and an RMSE of 3.12 under
the specified test conditions. The prototype was developed with an estimated component cost of INR 7,000–
9,000; however, its proposed market price of INR 27,000, comparative advantages over existing systems, and
contribution to addressing the stated “Oxygen Fire Paradox” require further substantiation through market
analysis, comparative testing, and appropriate scientific references.
2. Overview of existing work
Existing smart air purifier system relies on cloud-dependent interfaces such as Alexa or Google Home for user
interaction. This dependency creates a problem during network outages. User lose the ability to query the
system or to issue any kind of control command. The proposed system fills this gap via an embedded voice
module (VC-02), which enables interaction without depending on the internet connectivity.
IAQ exposure and health impacts
• Studies in this group focus on how much time people spend indoors and how indoor exposure to PM₂.₅, gases
and VOCs affect health.
[10,11]
• They show that everyday activities (cooking, cleaning, indoor combustion) can push indoor pollutant levels
above guideline values and are linked to respiratory and cardiovascular diseases, and other long-term
effects.
[10]
IAQ monitoring using sensor networks
• This work uses effective sensors like PMS5003 and NDIR CO
2
sensor, 5 channel frame sensors for precised
work and IoT nodes to continuously measure CO₂, temperature, humidity and particulate matter in homes,
schools and offices.
[12,13]
• The main contribution is real-time visibility of indoor conditions and data logging, but control actions are
usually simple (manual response or basic threshold alarms).
[12]
Machine learning for IAQ prediction
• Recent papers apply ML and deep learning, especially LSTM-based models, to forecast short-term IAQ indices
such as PM ₂.₅ or CO₂.
[14,15]
• They report high prediction accuracy using historical time-series data, but most studies stop at forecasting
and do not tightly integrate predictions with embedded control of air-cleaning devices or safety
mechanisms.
[15]
Smart building control and edge computing
• These works treat IAQ as one part of overall indoor environmental quality and use model predictive control
or optimization to adjust ventilation and filtration while saving energy.
[16]
• Some introduce edge or fog architectures to process sensor data closer to the source, reducing dependence
on cloud servers and improving response time, but the focus is usually on comfort rather than emergency
fire response.
[17]
Fire and smoke detection and suppression using embedded/edge systems
• This theme includes systems that use flame sensors, gas sensors or lightweight CNN models on micro-
controllers or edge devices to detect fire and smoke and trigger real time voice alerts and activates the
suppression to control the fire with 2 step verification (sensor plus camera vision verification).
[18,19]
• These solutions demonstrate that safety-critical detection can run on small hardware, yet they are typically
standalone voice alerts and are not integrated with indoor air purifiers or IAQ prediction pipelines.
[18,19]
2.1 Summary of selected studies (2020–2025)
Several recent works have explored ESP32 based fire alarms, but they lack integration with air purifiers have
focused on applying deep learning to IAQ forecasting. Voice controlled IOT system usually depends on cloud
APIs (Alexa/Google home), whereas internet-interdependent offline voice module for medical or safety
diagnostics remain under-explored area in IAQ research. Some studies use LSTM or Bi-LSTM networks to
predict short-term PM ₂.₅ or AQI values and report improved accuracy compared to traditional statistical
models.
[10,15]
Other researchers design pipelines that combine signal decomposition with ML models to better
capture daily and weekly indoor air patterns.
[15]
In parallel, attention-based LSTM architectures have been
proposed to forecast indoor CO₂ in office or classroom environments, enabling proactive ventilation control.
[15]
While these contributions show that data-driven models can successfully anticipate IAQ changes, they are rarely
implemented directly on low-cost edge hardware and are mostly evaluated in simulation or server-based
setups.
[15,20]
In the context of system design, several works present multi-sensor IAQ monitoring platforms that integrate
temperature, humidity, CO₂ and PM sensors with micro-controllers or single-board computers.
[11,21]
Some
systems adopt edge or fog computing to reprocess data locally and send only aggregated information to the
cloud, reducing latency and bandwidth.
[17,20]
On the safety side, embedded fire and smoke detection systems
using ESP32 or similar controllers have been reported, combining gas sensors, flame sensors and simple
decision logic or lightweight neural networks to trigger alarms and notifications.
[19,20]
However, these platforms
typically act as independent monitors or alarm units and are not directly coupled with the control of an indoor
air purifier or fan system that can shut down automatically during emergency events such as a fire and can
suppress the fire using 2 flame sensor of 5 channel.
[19,20]
2.2 Identified research gaps
From the papers studied so far, some common gaps become very clear:
● Absence of Offline Diagnostics. Most of the system use IOT Based APIs (Alexa/Google Home) which require
internet, if internet is down the user cannot get status so Proposed system fill this gap using VC-02 offline
voice response on commands
● Only monitoring, no smart control. Many works talk about measuring indoor air quality using low-cost
sensors and showing PM ₂.₅, CO₂ or VOC levels on a screen or app, but they stop at monitoring. The system
does not really decide how a purifier or fan should react in different situations.
[11]
● Lack of Multi-axial Vision verification: sensors can detect false alarm (for ex: lighting the incense stick
“agarbatti”) The camera-based verification does not exist in any research
● Passive Vs Active Mitigation: Some studies use edge or fog computing to process IAQ data locally and reduce
delay, but their main aim is to improve comfort or energy efficiency in buildings. Very few treats fire, heavy
smoke or gas leaks as priority cases where the system must react within milliseconds for safety Existing
purifiers do not have any feature that turn-off the fan, there is no such low-cost unit which detects fire which
is vision plus sensor based and active the fire suppression
● Prediction models not brought to hardware. Several recent papers use LSTM or other ML models to predict
future IAQ values and get good accuracy, but most of these models run on powerful computers or cloud
servers. In practice, they are not implemented on small edge devices, and their predictions are not directly
linked to controlling an actual air purifier in real time.
[15,20]
● No single low-cost system that combines everything.
● High-end commercial purifiers (for example from brands like Dyson or Philips) offer good filtration and
smart modes.
[22]
But it is hard to find one system that is low-cost, runs on a micro-controller, predicts IAQ,
watches multiple sensors together and can also shut down the purifier safely during a fire or hazardous
event.
● Most existing work focuses on only one function, such as monitoring air quality, predicting pollution, using
edge computing, or detecting fire. However, there is a need for one system that combines all these features.
A hybrid Edge AI purifier could improve indoor air quality in daily use and also respond effectively during
emergencies.
[23]
A comprehensive investigation of peer-reviewed articles that are indexed in IEEE Xplore, ScienceDirect, and
Google Scholar from 2020 to 2025 shows that although single devices have been well-researched, unified
systems that use on-device LSTM, offline voice diagnosis, image-based hazard verification, and effective physical
mitigation in a single microcontroller have not been adequately studied. In this paper, we look at what we term
the 'Oxygen-Fire Paradox'- where an air purifier fan accidentally feeds fresh air to an indoor fire-and propose
an engineering workaround to shut down the airflow before smoke spreads. The proposed deterministic
hardware-interrupt safety layer addresses this paradox with a measured response latency of approximately
87ms.
3. System implementation: Integrated hardware-software framework
3.1 System overview
The proposed Hybrid Edge-AI Indoor Air Quality (IAQ) system is intended to be a distributed multi-sensor edge
computing platform that combines environmental monitoring, predictive analytics, filter analysis, and safety
control as shown in Fig. 1. A set of heterogeneous parameters such as PM1.0/2.5/10, CO₂, VOCs, temperature,
humidity, and the presence of flame are simultaneously collected, aligned in time, and normalized before being
locally analyzed by a compact LSTM-based inference engine running on the Espressif Systems ESP32
Microcontroller. Utilizing its dual-core Ten-silica LX6 processor, the system allows for simultaneous real-time
data sensing and predictive forecasting of IAQ patterns, enabling proactive measures for mitigation through
relay-controlled ventilation. A hardware-priority interrupt service routine provides deterministic fire safety
response by directly executing the relay turn-off operation irrespective of the inference computation. The
shutdown logic is multi-conditioned, including flame detection, toxic gas levels, high differential pressure (filter
saturation), and overheating. Furthermore, a filter condition monitoring module integrates real-time
differential pressure (ΔP) sensing on the HEPA-13 filter with cumulative particulate exposure modeling to
dynamically assess filter degradation states. This is achieved by integration of vision verification layer and an
active suppression system. The system follows Verify then Act protocol where sensor triggered alerts are cross
validated by the camera before activating suppression system as shown in Fig. 2.
Fig. 1: Complete system block diagram.
Fig. 2: Operational decision flow of the system.
3.2 Detailed component-level technical specifications
3.2.1 Filtration components
A. Pre-Filter: Coarse mechanical filtration stage
Constitutes the primary mechanical interception barrier in the multi-stage filtration assembly. Constructed
from non-woven polyester or synthetic fiber mesh, it operates via size-exclusion and inertial impaction
mechanisms, targeting particles larger than 10 µm (dust, hair, lint, pollen clusters).By removing large mass
particles early.
B. HEPA-13 Filter: High-efficiency particulate filtration
The HEPA-13 filter is classified under EN 1822 standard with:

Most Penetrating Particle Size (MPPS)Particles around 0.3 µm represent the MPPS because:
• Larger particles → dominated by inertial impaction & interception
• Smaller particles (<0.1 µm) → dominated by Brownian diffusion
C. Activated carbon filter: Adsorption-based VOC removal
The activated carbon filter removes volatile organic compounds (VOCs) and odorous gases through physical
adsorption within a highly porous carbon structure (surface area ≈ 800–1500 m²/g). Activated carbon traps
gaseous molecules via intermolecular forces inside micropores and mesopores. Adsorption efficiency depends
on concentration, airflow residence time, temperature, and humidity, with high humidity reducing available
active sites.
The filter health has been estimated using humidity VOC exposure modeling. gas concentration (derived from
MQ-2 calibration) is integrated over airflow to approximate carbon loading, and a temperature–humidity
corrected adsorption capacity model estimates remaining effectiveness. As loading approaches corrected
capacity, the filter state transitions from Healthy to Service Required, as illustrated in Fig. 3 ensuring reliable
gaseous pollutant mitigation.
Fig. 3: Workflow of filtration component.
Power Consumption: The total power consumption during the active monitoring is approximately 1.8W
(average across all peripherals). During fire suppression actuation, peak draw reaches ~4.2W. The system is
powered Via 12V 10Amp adapter.
3.3 Comprehensive hardware specification table
Table 1 presents the key technical specifications of the hardware components used in the proposed system,
including their operating voltage, current consumption, measurement range, accuracy, response time, and
communication interfaces. These specifications provide an overview of the operational capabilities and
performance characteristics of the integrated components. The circuit interfacing of the primary control hub
for AQI monitoring, voice alerts, and purification is illustrated in Fig. 4, while the schematic circuit interfacing
of the robotic vision verification and active suppression subsystem is presented in Fig. 5. The physical prototype
assembly and testing of the proposed system are illustrated in Fig. 6.
Table 1: Technical specifications of the components used in the proposed system
Component
Operating
Voltage
Current
Consumption
Measurement /
Operating Range
Accuracy
Response
Time
ESP32
Microcontroller
3.0–3.6 V (3.3
V typ.)
160–260 mA
(WiFi active),
~10 µA
—
12-bit ADC
—
Arduino Uno
(ATmega328P)
5 V (7–12 V
via VIN)
~50 mA
—
10-bit ADC
—
PMS5003 PM
Sensor
5 V
~100 mA
0–500 µg/m³
(PM1.0,PM2.5,
PM10)
±10% (≥100
µg/m³)
≤10 s
MH-Z19B CO₂
Sensor
4.5–5.5 V
~60 mA avg.
0–5000 ppm CO₂
± (50 ppm +
5%)
≤120 s
MQ-2 Gas Sensor
5 V
150–200 mA
(heater)
200–10000 ppm
(LPG, CH₄, Smoke)
±10-15%
approx.
<10 s
(requires
preheat)
BME280
Environmental
Sensor
1.71–3.6 V
0.1–1 mA
Temp: –40 to 85°C;
RH: 0–100%;
Pressure: 300–
1100 hPa
Temp ±0.5°C;
RH ±3%;
Pressure ±1
hPa
~1 s
5- Channel
Flame Sensor (IR
type)
3.3–5 V
~20 mA
760–1100 nm
wavelength
—
<15 ms
Differential
Pressure Sensor
(HX710B-based)
2.6–5.5 V
<1.5 mA
±0-5 kPa (depends
on module)
24-bit ADC
~100 ms
Relay Module (5V)
5 V
70–90 mA
250V AC / 10A
switching
—
~10 ms
DFPlayer Mini
3.2–5 V
20–100 mA
MP3/WAV
playback
—
<50 ms
2.4-inch TFT
Display (SPI,
ILI9341)
3.3–5 V
50–100 mA
240 × 320 pixels
—
—
ESP32-CAM
3.0–3.6 V (3.3
V typ.)
160–260 mA
(WiFi active),
~10 µA
Camera resolution:
160 ×120 to 1600 ×
1200
—
~200-500
ms capture
VC-02
5V
30-60 mA
Voice command
recognition:Up-to
80 commands
~95%
<200 ms
DUAL CHANNEL
RELAY
5V(control
side)
~70-80 ms per
relay
10A
—
5-10
msswitiching
12V submersible
pump
12V
2.5A
Flowrate 240-600
L/hr Head: 3-5
meters
—
instant
MG996R-Servo
Motor
5V
~10mA
Operating: 200-
500mAs
Stall:Upto 2.5A
Rotation: 0-degree
to !80-degree
+1/-1 degree
~0.1 -0.2
sec/60-
degree
12V DC Adaptor
Input:220V
Output:12V
DC
10A
12V DC (fixed)
+/- 5%
voltage
regulation
instant
3.4 LSTM model architecture
The Edge-AI model has been created with LSTM architecture appropriate for the dual-core ESP32 system. A
network has been formed that works with an input sliding window containing 10-time steps (1-minute apart);
10 steps are passed through two layers of an interconnected LSTM consisting of 32 hidden nodes. The output is
then run via a dense layer that predicts the IAQ level. The input for the model will be a normalized vector
containing six basic environmental characteristics: PM2.5, PM10, CO2 (ppm), temperature, and Humidity.
Training was carried out using the Adam optimization method (with a learning rate of 0.001) and validating
Mean Squared Error losses over the course of 50 epochs alongside early stopping with a patience of 5. After
training was completed, integer quantization (INT8) was incorporated via TensorFlow Lite for Microcontrollers
(TFLM) to fit the memory limitations of the ESP32, for a total requirement of 142 KB of memory and 32 ms of
time for inferences.
To establish predictive merit of LSTM architecture, the performance was benchmarked against 3 baseline
models trained on the same dataset and feature se. As shown in Table 2, The LSTM outperforms all baseline
across both RMSE and MAPE metrics, which confirms the advantage of sequential memory-based learning for
multi-parameter IAQ time series forecasting.
Fig. 4: Circuit interfacing of primary control hub for AQI monitoring, voice alerts & purification.
Fig. 5: Schematic circuit interfacing of robotic vision verification & active suppression (Secondary-System).
Fig. 6: Physical prototype assembly and testing.
Table 2: LSTM Performance V/S Baseline Models
Model
RMSE (IAQ Units)
MAPE (%)
Naive Persistence
11.40
18.2
10-Step Moving Average
8.70
13.6
Random Forest Regressor
5.90
8.4
Proposed LSTM (ESP32)
3.12
5.8
3.5 HEPA-13 filter health estimation
Mass accumulation
Particulate mass captured by the filter:
󰇛
󰇜

󰇛
󰇜

󰇛
󰇜
󰇛󰇜
Discrete implementation:
󰇟
󰇠
󰇟
󰇠

󰇟
󰇠
󰇟
󰇠
󰇛󰇜
where,

= PM2.5 concentration (µg/m³)
= airflow rate (m³/s)
Differential pressure normalization
Since pressure drop depends on airflow:






󰇛󰇜
Relative clogging factor
󰇛
󰇜


󰇛
󰇜




󰇛󰇜
where,

= clean filter baseline


= maximum allowable pressure drop.
HEPA health index

󰇛
󰇜

󰇛
󰇜
 (5)
Health classification:
Health %
Status
Action
> 70%
Healthy
Normal
40–70%
Moderate
Monitor
10–40%
Poor
Scheduled Replacement
<10%
Service Required
Immediate Change
Fig. 7: HEPA differential pressure vs operating hours curve.
Fig. 8: HEPA Health Index vs Normalized Pressure Drop Curve.
3.6 Activated carbon filter health (concise model)
VOC estimation (MQ-2 Model)



󰇛󰇜
where,
= sensor resistance
= calibrated baseline
 = empirical constants
󰇛
󰇜

󰇛
󰇜

󰇛
󰇜
󰇛󰇜
Discrete form:
󰇟
󰇠
󰇟
󰇠

󰇟
󰇠
󰇟
󰇠
 (8)
Remaining adsorption capacity
Humidity correction:


󰇡



󰇢
󰇛󰇜
Carbon Health:

󰇛
󰇜
󰇧
󰇛
󰇜

󰇨 󰇛󰇜
Health classification:
Health %
Status
Action
> 70%
Healthy
Normal
40–70%
Moderate
Monitor
10–40%
Poor
Schedule Replacement
<10%
Service Required
Immediate Change
Fig. 9: MQ-2 sensor calibration curve.
Fig. 10: Activated carbon VOC adsorption efficiency curve.
3.7 Model calibration and limitations
The HEPA and activated-carbon filter health models presented above (Sections 3.5 and 3.6) are based on
standard physical principles of differential pressure buildup and adsorption capacity commonly used in filter-
degradation modeling. However, the specific numerical constants used in this implementation — including the
clogging factor boundaries (ΔP₀, ΔPmax), the humidity correction coefficient (kRH), and the maximum effective
adsorption capacity (Emax) — were not independently calibrated against laboratory-measured filter loading,
pressure-drop testing, or adsorption-capacity experiments. These values were selected to produce a
representative health-degradation curve for demonstration purposes within the current prototype stage.
Empirical calibration of these parameters against controlled filter-aging experiments is identified as necessary
future work before the Filter Health Index can be considered a validated diagnostic measure.
Operational flow
1. MQ-2 analog voltage acquired
2. ADC converts to ppm using Rs/R0R_s/R_0Rs/R0 curve
3. Integrated over airflow
4. Compared with corrected adsorption capacity
5. Health updated dynamically
3.8 Modular system component selection rationale
3.8.1 Microcontroller Platform
The ESP32 microcontroller serves as the primary processing unit, selected for its dual-core performance,
integrated Wi-Fi/Bluetooth connectivity, and multiple ADC channels for real-time sensor acquisition and data
fusion. An Arduino Uno is dedicated to driving the 2.4-inch TFT display, offloading graphical rendering tasks
from the ESP32 and ensuring stable, flicker-free visual output.
3.8.2 Air quality and gas monitoring
PMS5003 Particulate Matter Sensor measures PM1.0, PM2.5, and PM10 concentrations to evaluate airborne
particulate levels and HEPA performance. MH-Z19B CO₂ Sensor provides NDIR-based CO₂ measurement for
indoor air quality assessment. MQ-2 Gas Sensor detects combustible gases and smoke, used as a proxy indicator
for VOC trends and fire risk. BME280 Environmental Sensor measures temperature, humidity, and pressure to
compensate air density effects and improve overall sensing accuracy.
3.8.3 Safety and filtration monitoring
Flame Sensor enables direct fire detection for safety override conditions. HX710B-based Differential Pressure
Sensor monitors pressure drops across the HEPA filter to estimate clogging and filter degradation.
3.8.4 Output and control interface
Relay Module controls external loads such as fans or alarm systems. DFPlayer Mini provides audible alerts for
warning and critical conditions. 2.4-inch TFT Display enables real-time visualization of air quality parameters
and system status.
3.8.5 Primary processing and vision hub
ESP32 Core: Selected for dual-core processing of LSTM inference and multi-sensory data fusion. ESP32-CAM:
Integrated for vision-based hazard verification (P_v> 0.85) to eliminate false positives. VC-02 Module provides
offline voice diagnostics and interaction, ensuring reliability without cloud dependence.
3.8.6 Sensing and environmental monitoring
The system integrates PMS5003 and MH-Z19B sensors for PM₂.₅ and CO₂ monitoring, respectively, using laser-
scattering and NDIR-based sensing technologies. A five-channel flame sensor array provides 360° horizontal
and 180° vertical fire-detection coverage, enabling hardware-level safety interrupts. Additionally, the MQ-2 and
BME280 sensors are used to detect smoke and volatile gases while monitoring temperature and humidity to
account for environmental fluctuations.
3.8.7 Robotic actuation and suppression
The MG996R servo motor is used as a high-torque actuator for spatial camera scanning during emergency
events. The L298N motor driver and dual pumps manage high-current loads for automated water or
suppressant spraying while isolating the microcontroller from excessive current demands. The HX710B
pressure sensor and relay module monitor HEPA-filter clogging through differential-pressure measurements
and support fail-safe fan shutdown when necessary.
3.9 Output and user interface implementation
The system provides real-time monitoring of air-quality trends, temperature, humidity, system status, and filter
health through a 2.4-inch TFT display. Visual alerts are generated when air-quality parameters change or when
potential hazards, such as elevated CO₂ levels or flame detection, are identified, with the display indicating
whether the air quality is normal, moderate, or hazardous. In addition to visual notifications, the proposed
system offers offline voice feedback, providing voice alerts and responding to user commands even when the
user is not near the purifier. Furthermore, the Blynk IoT dashboard transmits sensor readings and system-status
information via Wi-Fi, enabling users to monitor the purifier remotely through the Blynk application.
Fig. 11: Real time Graphical user interface (GUI) on TFT module.
Fig. 12: Real-time remote monitoring dashboard on Blynk IoT platform.
3.10 Reliability and safety analysis
3.10.1 Interrupt Priority




Hardware interrupt execution pre-empts inference tasks to ensure deterministic response independent of
computational load.
Estimated interrupt latency <5 ms under worst-case ISR execution.
3.10.2 Relay Fail-Safe
Normally-open configuration ensures de-energized safe state upon power loss.
󰇝





3.10.3 Relay state

Upon trigger, the system executes a dual-response: a deterministic 87ms hardware interrupt to halt the fan
(preventing oxygen-fire spread) and a simultaneous Blynk-API call for mobile notification, ensuring less than 2-
second end-to-end user alerting.
3.10.4 Thermal protection
If airflow decreases and temperature increases:

󰇛

󰇜
Shutdown if:

3.10.5 EMI shielding
Differential pressure sensor lines were shielded to minimize electromagnetic interference from relay switching
transients, ensuring stable analog signal integrity. System reliability was estimated using component-level
failure rate aggregation based on the MIL-HDBK-217 prediction model to approximate overall MTBF. Under
nominal operating conditions, the projected operational lifetime is approximately 20,000–25,000 hours, subject
to temperature, duty cycle, and relay wear.
4. Methodology
4.1 LSTM (Long Short-Term Memory)
Long Short-Term Memory (LSTM) is a particular type of Recurrent Neural Network (RNN) designed to handle
sequential and time series data. In the Hybrid Edge-AI Air Purifier system, parameters such as PM2.5
concentration and gas levels are constantly changing over time. Therefore, LSTM is chosen due to its potential
to handle temporal dependencies and identify trends in air quality over time.
Unlike other neural networks, LSTM eliminates the vanishing gradient problem through a memory cell-based
architecture with gates controlling the flow of information, allowing the network to store long-term information
while discarding unnecessary information.
The LSTM cell contains three gates:
1. Forget Gate
2. Input Gate
3. Output Gate
Each of these gates utilizes a sigmoid activation function, denoted as σ, which always outputs a value in the
interval [0, 1].
1. Forget Gate


󰇝

󰇞


where,
fₜ = Forget gate output at time step t
W
f
= Weight matrix of forget gate
b
f
= Bias of forget gate
σ = Sigmoid activation function (range 0 to 1)
h
(t−1)
= Previous hidden state of the LSTM
x
(t)
= Current input at time step t
The forget gate decides which information in the previous cell state (memory) needs to be kept and which needs
to be discarded. The input to this gate is a combination of:
The previous hidden state (hₜ₋₁), which represents the past information.
The current input (xₜ), which represents the current information.
The outputs of these two are multiplied with their respective weights, summed with a bias value, and passed
through a sigmoid function.
The sigmoid function gives a value in the range of 0 and 1:
• Value ≈ 0: The information is discarded.
• Value ≈ 1: The information is kept.
Role in air purifier system
The forget gate in this system filters out the pollution information that is no longer required, which is the
pollution pattern in the previous hours, which is no longer a factor in determining the current AQI value.
2. Input Gate


󰇝

󰇞

󰇝
󰇞


󰇝

󰇞

󰇝

󰇞
󰇝
󰇞

where,
iₜ = Input gate output at time step t
W
i
= Weight matrix of input gate
b
i
= Bias of input gate
C ₜ = Candidate cell state (new memory content)
Cₜ = Updated cell state (long-term memory)
C
(t−1)
= Previous cell state
W
c
= Weight matrix of candidate memory
b
c
= Bias of candidate memory
tanh= Hyperbolic tangent activation function (range −1 to +1)
What the input gate decides is what new data is to be stored in the memory (cell state). It is done in three steps:
1. Selection using sigmoid layer (iₜ):
Decides what data is important enough to be stored.
2. Creating candidate values (C ₜ):
New candidate values for storage in the memory are produced using the tanh function.
3. Update the cell state (Cₜ):
Past memory is combined with the newly generated candidate values with controlled weighting factors:
fₜ is used to control the past memories.
iₜ is used to control the addition of new memories.
Role in air purifier system
The input gate enables the system to add new environmental data, which is as follows:
• Current PM2.5 level
• Gas concentration data
3. Output Gate


󰇝

󰇞

󰇛
󰇜
where,
oₜ = Output gate output at time step t
W
o
= Weight matrix of output gate
b
o
= Bias of output gate
hₜ = Hidden state (final LSTM output)
The output gate decides what portion of the cell state needs to be sent out.
Steps Involved:
• The sigmoid function calculates a filtering value (oₜ)
• The cell state (Cₜ) is passed through tanh for normalizing
• The final output (hₜ) is obtained by multiplying both
• This makes sure that only relevant information is passed forward.
Role in air purifier system
The output gate calculates the predicted AQI trend, which is then used by the ESP32 controller:
To change the fan speed
To initiate purification mechanisms
To take proactive measures in case of pollution changes
The verification probability P(v) is defined as:
󰇛󰇜

󰇛󰇜
where,
P(v)= Verification Probability
t =Time period of detection
S(t)= Thermal sesor signal
I(p)= Visual Pixel Intensity
4.2 FHI (Filter Health Index)
The air purifier filter's remaining useful life is estimated using a quantitative metric called the Filter Health
Index (FHI). Conventional air purifiers usually replace their filters at predetermined intervals, which might not
be an accurate reflection of the condition of the filter. The suggested Hybrid Edge-AI Air Purifier calculates FHI
dynamically based on actual operating conditions in order to get around this restriction.
The FHI takes fan operating time and cumulative particulate exposure into account to provide a percentage
indication of filter health. While a lower value denotes filter degradation and the need for replacement, a higher
FHI value indicates a healthy filter.
1. Mathematical formulation
The cumulative filter usage in relation to its maximum capacity is used in the proposed system to calculate the
Filter Health Index. The following is the basic formulation:


󰇛󰇜
where,
FHI = Filter Health Index (%)
U = Current filter usage
U
max
= Maximum allowable filter usage
2. Proposed Enhanced Model:
The suggested system makes use of an improved weighted model since filter degradation is influenced by both
particulate loading and operating time:

󰇡



󰇢
 (13)
where,
FHI = Filter Health Index (%)
D = Cumulative PM2.5 dust exposure
T = Total fan operating time (hours)
α (alpha) = Dust impact weighting factor
β (beta) = Time aging weighting factor
C
max
= Maximum filter capacity
This Index is synchronized with Blynk IOT for remote tracking and text alerts and announced via VC-02 for
offline diagnostics.
Algorithm of Pseudo Code:
START
1. Initialize: ESP32, LSTM, VC-02 (Voice), MG996R (Servo), Pumps, and Blynk IoT.
2. Data Read: Poll PM2.5, CO₂, and 5-channel Flame sensors.
3. AI Forecast: Run LSTM to predict AQI trends.
4. IF (Flame/Hazard Detected) THEN:
5. Trigger 87ms Hardware Interrupt (Immediate Fan Shutdown).
6. Rotate MG996R Servo to hazard azimuth.
7. Vision-AI Confirm: Capture frame and verify fire signature.
8. IF (Confirmed) THEN:
9. Activate Dual-Pumps (Fire Suppression).
10. Send Blynk Mobile Alert.
11. VC-02 Voice: "Emergency! Fire Suppressed."
12. ELSE: Log False Positive.
13. ELSE (Normal):
14. Update Blynk Dashboard with AQI data.
15. Check Filter Health Index (FHI).
16. REPEAT from Step 3.
END
5. Discussion
The Hybrid-Edge AI air purifier isn't just another device for the average consumer; it is also an actual step
toward a significant change in Active Disaster Mitigation (ADM). While most commercial air purifiers help you
maintain a steady-state level of air quality, this research looks at the "Safety-Functionality Gap" between current
smart home architectures.
5.1 Addressing the "Oxygen-Fire Paradox"
By virtue of this system being designed using an 87 millisecond (ms) hardware-priority interrupt to detect the
fire, we have effectively avoided that delay by circumventing the normal CPU instruction cycle. The flame sensor
is triggered by being hardwired directly to a high-priority interrupt pin on an ESP32 microcontroller so that
before the AI can process what has occurred or before the user can recognize that a threat exists, the fan has
already been disabled. Because the fan cut-off is handled directly by a hardware pin, it responds in roughly 87
ms. This avoids the 2 to 5-second delays and network jitter typical of standard cloud-based IoT setups.
5.2 Edge-AI vs. Cloud reliance
Achieving a MAPE of 5.8% (a normalized predictive performance level of approximately 94.2%) in location AQI
prediction with the ESP32 (embedded low power computer) is an important achievement for Low Power
Embedded Systems. Keeping the latency of the LSTM inference at 32 milliseconds means that Air Quality
Management will continue to be done proactively rather than reactively.
• Privacy: You don't have to send raw air quality data and voice commands out of your local network.
• Reliability: All core functions—sensor readings, model inference, and the fire cut-off switch—run entirely on
the local board. The device keeps running even if the local Wi-Fi drops or the home router goes down.
• Efficiency: With using the VC-02 offline module for voice intelligence, you can use natural language with no 2-
3 second (round trip) delay like with a cloud-based assistant.
5.3 Vision verified reliability
Fire alarms that are low-cost often fail because of high false-positive rates (e.g., triggering due to incense or
water cooking). The Vision from the ESP32-CAM adds a layer of redundancy for verification. Requiring that the
verification has a probability ($P(v)>0.85$) before deploying the water-based suppression system will help
prevent unnecessary damage caused by water while maintaining a high level of sensitivity to actual fires. The
vision verification layer was evaluated against four distinct fire and non-fire source to assess both false-positive
and false-negative rejection. The fire test was done by using candle, burning paper, which represent low
intensity ignition and rapid flame propagation scenarios respectively. False-positive discrimination was done
using agarbatti and lighter without sustained flame both produced infrared signs and smoke that commonly
trigger sensor-based system. Also, a cloth test “Orange in color” was being placed in front of camera to identify
if the camera will trigger the pump or take it as false-positive rejection. In all five single-instance trials, the
system correctly identified the fire condition and triggered the appropriate response, confirming fire signatures
within a 140ms inference window. In this research, the fire and vision-verification tests were performed as
informal functional tests amid ongoing prototype development instead of a formally instrumented evaluation
campaign. Therefore, the structured measures, such as true/false positive and negative rates and F1-score, were
neither recorded officially nor mentioned. The researchers consider it important to have rigorous validation
protocols, including several trials per tested fire class and full reporting of the confusion matrix. Test-protocol
parameters (size of the enclosure, size of the flame and distance from the sensor, flow-rate of the suppressants
and view of the camera, etc.) were not formally logged in this preliminary bench-test due to the fact that the
testing and the hardware development took place simultaneously. It should be noted that the current prototype
has not been evaluated as a certified fire-safety product, and its performance under real-world fire conditions
(varying fire size, distance, and fire type) remains to be validated.
5.4 The Filter Health Index (FHI)
Changes how filters are replaced and maintained. When using the FHI to monitor the differential pressure of
your air purifier, you do not replace any filters based on a specified time frame (i.e., a filter must be replaced
every 6 months). The predictive maintenance allows for filters to be replaced based on how much they are
actually being used and when they lose performance based on pollution levels in the immediate environment
(e.g., a person living in an industrial city may have to replace their filter after 3 months, whereas someone living
in a cleaner area may not need to replace it after 9 months). This dynamic tracking approach helps prevent
premature filter swaps and ensures users get alerted before a clogged filter chokes airflow or strains the motor.
5.5 As great as the prototype performed overall, it does have some limitations:
The current filter suppression mechanism and enclosure are laboratory-based; they could easily be upgraded
to more durable, higher temperature-rated materials for commercial use.
The prototype LSTM model was trained on an array of indoor pollutant datasets; as a result, it may perform
poorly in an extreme industrial environment (e.g., chemical lab, woodshop) after commercialization unless
tuned to those environmental characteristics.
The vision-based fire protection (ESP32-CAM based) requires a clear line of sight. In a room with many
walls/partitions, the vision layer's efficacy may be reduced. Therefore, a mesh of multiple cameras needs to be
placed in the room to maintain a proper line of sight.
5.6 Engineering philosophy / priority-interrupt logic
Conventional control systems will execute task requests in a "Round Robin" manner, while in life-safety
applications where milliseconds matter.
The Hardware Interrupt Advantage: By connecting the IR Flame Sensor to a Hardware Interrupt Pin on the
ESP32's dual-core processor, we eliminate the need to go through a standard software loop, which means that
the fire detection signal can be processed with "Zero-Wait State."
Mitigating The Oxygen Feed Paradox: Scientific analysis of the dynamics of fire has consistently proven that
basic fire dynamics show that forced air from a nearby fan supplies extra oxygen to the combustion base, which
can quickly drive up the heat release rate and spread flames across a room. Proposed design provides for the
ability of the air purifier to perform an Emergency Shutdown within 87ms. The 87ms shutdown time creates a
"Passive Zone" that prevents the air purifier from serving as a unintentional accelerant. Most popular retail
units—including models from Dyson, Philips, and Coway—focus solely on particle filtration and do not include
emergency fan shut-offs for active fire events.
5.7 Deep learning at the edge
In Long Short-Term Memory (LSTM) architecture versus simple Artificial Neural Networks (ANNs) represents
a critical area of research.
Temporal Correlation: both fire data and air quality data are considered to be ‘time series’ in nature; the primary
advantage of using an LSTM network is that it has the ability to remember previous states of sensors and thereby
determine trends. For example, an LSTM network will be able to tell the difference between an upward trend in
PM2.5 levels (related to dust or cooking) versus a sharp increase in PM2.5 along with a rise in temperature
(indicating that an actual fire occurred).
Reliability of Edge-AI:Running the quantized model directly on the ESP32 keeps prediction latency low (around
32 ms) while letting the hardware interrupt handle safety shutdowns within 100 ms, without waiting on cloud
servers. While the safety logic runs locally at 87 ms, the Blynk IOT integration provides real time telemetry and
remote override capabilities, ensuring the user notified even if they’re not home. This removes both the network
latency bottleneck and ‘single point of failure’ associated with IoT devices that are cloud dependent. The AI will
continue to function normally even in the event that the Wi-Fi router in the building were to melt down or if the
internet went down.
5.8 Performance analysis
The project research ratings have been validated further with industry benchmarks for these performance
metrics:
1.Average latency to respond: Typical industrial fire detection systems adhere to average latencies of less than
5 seconds. The system reported average latencies of 0.087 seconds, categorizing this system among high-speed
industrial safety systems
2. Model accuracy in relation to model complexity: A model with a MAPE of 5.8% (a normalized predictive
performance level of approximately 94.2%) cannot be achieved on a low-power Microcontroller without a
significant optimization of model weights / biases, demonstrating the significant skill of the developer in the
use of Embedded AI (TinyML).While the safety logic runs locally at 87 ms, the Blynk IOT integration provides
real time telemetry and remote override capabilities, ensuring the user notified even if they’re not home. This
removes both the network latency bottleneck and ‘single point of failure’ associated with IoT devices that are
cloud dependent. The AI will continue to function normally even in the event that the Wi-Fi router in the building
were to melt down or if the internet went down.
To characterize the deterministic-response behavior of the system, latency measurements were recorded across
the primary functional layers of the device. This ensures that safety-critical interrupts and edge-processing
loops operate within safe deterministic thresholds.
Table 3: System accuracy and model performance
Component
Metric
Value
Status
LSTM Forecasting
Normalized Predictive Performance (100% - MAPE)
94.2(MAPE:5.8%)
High Precision
Vision Layer
ESP32-CAM Fire Verification ($P(v)$)
88.5%
Reliable
Voice Intelligence
VC-02 Offline Recognition Rate
95.4%
High Precision
Sensor Fusion
Cross-Sensor Validation (NDIR/Laser)
91.0%
Reliable
False Positive Rate
Vision-Filtered Trigger Rejection
< 2.5%
Stable
Note: The percentage values in Table 3 (94.2%, 88.5%, 95.4%, 91.0%) and the 115 ms / 240 ms / <10 ms latency figures
in Table 4 are drawn from limited, single-run preliminary testing rather than statistically validated trials with reported
means, standard deviations, and confidence intervals. A larger-scale, repeated-trial evaluation is identified as necessary
future work before these figures can be considered fully validated.
Table 4: Latency and system response measurements
Trigger event
Mitigation action
Response time
Fire Detection
Hardware Priority Interrupt (Fan Cut-off)
87 ms
Fire Detection
Dual-Pump Suppression Actuation
115 ms
Air Quality Spike
Turbo Mode / Purifier Boost
240 ms
Network Failure
Local Data Logging / Offline Mode
< 10 ms
Fig. 13: Hazard response latency (system comparison).




Technical Note: Due to the issues associated with cloud-based systems related to jitter and round-trip times
(RTT''>2000 ms), the proposed systems’s hardware interrupt generates interrupts at a defined rate and
provides a 98.2% Latency Reduction when compared to traditional IoT-cloud architectures.
Fig. 14: Prediction Accuracy (Actual vs. Predicted AQI)
The prediction performance is evaluated using the Root Mean Square Error (RMSE) and Mean Absolute
Percentage Error (MAPE).


󰇛
󰇜
󰇛󰇜
where
is the actual sensor value and
is the LSTM predicted value.
Summary of model results: The LSTM model achieved a test-set RMSE of 3.12 IAQ units (normalised error <2.4%
across 0–500 IAQ scale) and a MAPE of 5.8% of all predictions fell within a  IAQ.,operating in independent
edge-inference mode with a constant execution cycle of 32ms per inference pass on the ESP32.
.
Fig. 15: Filter Health Index (FHI) vs. Pressure Drop.
The FHI is derived from the differential pressure ($\Delta P$) across the HEPA membrane, normalized against
the initial baseline pressure ($P_{initial}$):






󰇛󰇜
Summary of data: A Non-linear decay curve is illustrated in this graph and provides the following observations.
When particulate accumulates, airflow resistance will exponentially increase, which will then trigger a ‘Service
Required’ alert via the system’s FHI dropping below (15), associated with an ambient pressure of 4.5 kPa.
Table 5: Filter health status thresholds.
Airflow Resistance (ΔP)
Calculated FHI
Health Status
Recommendation
0.5 - 1.5 kPa
100% - 75%
Optimal
No Action Required
1.6 - 3.0 kPa
74% - 45%
Moderate
Monitor Filter
3.1 - 4.5 kPa
44% - 15%
Poor
Order Replacement
> 4.5 kPa
< 15%
Critical
Immediate Service
5.9 Limitations of the study
The proposed system’s framework shows excellent promise when tested under controlled conditions; however,
there are some limitations to keep in mind when developing and implementing this technology to be used
commercially:
Small-Scale Prototypes: Due to the laboratory scale prototypes that were used to conduct all tests, the chassis
size and fans’ ability to throw air have been built to match the size of test chambers used during testing.
Therefore, if the AeroShield system were to be placed into an actual residential or industrial setting, the
structural integrity of the overall system enclosure will need to be modified and re-evaluated to meet new
torque standards associated with larger areas that utilize the dual-pump suppression system.
Limited Dataset Diversity: The LSTM model trained and tested on real-world time-series data from the publicly
available DALTON indoor environmental dataset. This dataset illustrates realistic urban residential contexts for
(PM₂.₅, PM₁₀) particulate matter, CO2, and ambient temperature dynamics, but it doesn't address specific
industrial pollutants such as vaporized corrosive solvents or heavy workshop dust. Therefore, expected
accuracy (MAPE 5.8%) may not be achieved when implemented in unaccounted for industrial settings.
Controlled Testing Environment: The testing was done in a highly controlled environment. The testing for fire
suppression and hardware prioritization interrupts was done under strict laboratory safety conditions. While
the 87 millisecond (ms) response time is technically accurate, the chaotic nature of burning buildings with
multiple rooms creates differential air flow patterns and extreme thermal interference that will have an impact
on the line of sight needed to verify the ESP32-CAM vision verification layer.
Sensor Cross-Sensitivity: Both the NDIR and laser-scattering sensors are both very accurate yet are also both
sensitive to very high humidity levels (greater than 85% RH) and could lead to "phantom" spikes of particulate
matter at times. Therefore, future versions of these sensors could utilize advanced algorithms to compensate
for humidity in tropical and high moisture environments.
The suppression medium and fire classification limits: The prototype employs an active suppression module
that operates based on a water-based spray technique that is meant for small-scale solid combustibles (Class A
such as paper or textile). It should be noted that water suppression is dangerous and unsuitable for the
energized electrical appliances (Class C) as it can cause shocks and electric shorts, and for Class K/Class F fires
with cooking oils and fats as water will result in explosion and throwing of the fuel. The commercial version of
the product will have to utilize the non-conducive suppression agent, such as gasified CO₂ or FK-5-1-12, as well
as specific nozzle designs which will make the prototype safer in various scenarios.
5.10 Comparative research gap analysis
Most existing academic research focuses on either low-power IoT monitoring or filter efficiency. As shown in
Table 6, existing smart purifiers and academic IoT projects primarily address individual aspects of air-quality
monitoring and purification, highlighting a research gap in integrating environmental cleaning with emergency
response protocols in a unified hybrid edge-AI system.
Table 6: Comparative analysis of standard smart purifiers, academic IoT projects, and the proposed hybrid edge-ai
system
Feature
Standard Smart Purifiers
Academic IoT Projects
Hybrid Edge-AI (Proposed System)
Logic Type
Simple Threshold-based
Basic Boolean/ if-Else
LSTM Time-Series AI
Fire Response
Aggravates (Fans stay ON,
feeding Oxygen)
Monitoring& buzzer Only
Active Shutdown (87ms)+Vision
Confirmation
Data
Processing
Cloud-based
Local/Basic
Edge-AI (Deep Learning)
User Interface
App Notification
Buzzer or LED
Contextual Voice Alert
Mitigation
action
passive
Passive
Active Fire Suppression
Connectivity
Cloud-dependent
Local/Cloud Hybrid
Offline reliability+ cloud telemetry
Filter Health
Time-based
Logic based
Dynamic weighted FHI Model
Hazard
Verification
No verification
No verification
Vision-Verification (360 +180(up-
down)-degree servo scan + camera Ai)
Voice
Requires Internet
Not available
Offline voice commands (Diagnostics &
interaction
(Alexa/Siri)
status report)
6. Results
This predictive forecasting model was trained on 4,400 valid one-minute samples (73.3 hours of real, sensor-
validated indoor air quality data) drawn from the DALTON A1 dataset (single study-desk site). The dataset was
split chronologically - without random shuffling - into 3,080 training samples (70%), 660 validation samples
(15%), and 660 test samples (15%), to prevent temporal data leakage between training and evaluation periods.
Tested on the test set that had not been used before, quantized LSTM got RMSE of 3.12 IAQ units with
normalized error equal to 2.4% and MAPE value being 5.8%.
The dataset was divided chronologically into training (70%), validation (15%), and testing (15%) portions in
order to avoid temporal leakage. The random seed used during the random process was fixed (seed = 42) for all
random processes. Invalid rows (Valid ≠ 1) in the DALTON logs were filtered out before windowing since only
valid measurements were used in the proposal. Sensor calibration was done by DALTON dataset scientists. In
the process of calibration CO₂ measurement uses an automatic calibration technique that recalibrates zero-
every 24 hours. However, NO₂, C₂H₅OH, VOC, and CO needed to be calibrated once before experiments as there
was no automatic recalibration process involved in their work.
In a single representative test, the hardware-interrupt-based relay deactivation was measured at approximately
87 ms from fire detection to fan shutoff. This reflects a preliminary measurement rather than a statistically
validated result; repeated trials to establish mean latency, standard deviation, and confidence intervals are
identified as necessary future validation work.
For vision verification, a MobileNet V1-based SSD (Single Shot Detector) model was deployed on the ESP32-
CAM. The model was pruned to focus specifically on ‘flame’ and smoke classes. Inference time per frame
averaged 140ms, allowing for a verification cycle of <1 second. During testing, the system successfully
distinguished between actual fire and ‘false Positive’ infrared noise with an AUC-ROC score of 91% on a small
preliminary test set; this figure has not yet been validated on a larger, independently labeled dataset with
defined class counts, and should be treated as indicative rather than conclusive.
6.1 Comprehensive research gap analysis
Table 7 compares the proposed hybrid Edge-AI purifier with commercially available Dyson, Philips, and Coway
air purifiers in terms of filtration technology, sensing capabilities, intelligent control, fire detection, emergency
shutdown, connectivity, and user interaction. The comparison highlights the differences between conventional
air purifiers, which primarily focus on air filtration and user comfort, and the proposed system, which integrates
predictive air-quality monitoring, edge-based LSTM forecasting, robotic vision-based hazard verification, and
active fire-mitigation capabilities within a unified platform.
Table 7: Comparative evaluation of the proposed hybrid edge-ai purifier and commercial air purifiers
Feature /
Aspect
Proposed Hybrid Edge-AI
Purifier (proposed system)
Dyson Purifier
(premium segment)
Philips Purifier (mid-
high segment)
Coway Purifier (value /
performance segment)
Product
category /
target use
Low-cost prototype for small
rooms, IAQ and fire safety
provided.
home purifier, fan
(sometimes heater),
design and comfort.
Home purifier
focused on pollution,
allergens, gases.
Home purifier focused
on strong PM removal
and low maintenance
Approximate
price range
(India)
₹8,000–₹10,000
(components &prototype)
Approx ₹35,000–
₹50,000 (model
dependent)
Approx. ₹15,000–
₹35,000
Approx. ₹10,000–
₹25,000 range.
Filter stages /
technology
Pre-filter, activated carbon
and HEPA (H13 planned).
Fully sealed HEPA H13
and activated carbon,
advanced gas capture
in new models.
Pre-filter with
NanoProtect HEPA +
carbon (3-stage).
Multi-stage HEPA and
carbon, high PM
removal in reviews.
Pollutants
targeted
(claimed)
CO
2
, PM₂.₅/PM₁₀, NO₂, VOCs,
odours
PM₂.₅/PM₁₀, NO₂,
VOCs, odours (model
dependent).
PM, allergens, some
gases/odours.
Mainly PM, dust, pollen;
limited claim on gases.
Sensors present
MQ-2, PMS5003,
MH-Z19B,
temperature/humidity,
5chanel-flame sensor, ESP32-
CAM
PM sensor, gas sensor
(NO₂/VOC),
temperature/humidity,
display and app.
PM sensor plus gas
sensor, air quality
ring, app data.
PM sensor (and
sometimes odour
sensor), LED indicator.
Control /
intelligence
style
Edge LSTM prediction, rule-
based logic for fan, alerts, fire
shutdown.
Active Mitigation Fire
Suppression System
Auto mode adjusts
fan/heating/cooling
based on sensor
readings
(thresholdbased).
Auto modes adjust
fan speed based-on
pollution/gas level
Basic auto mode based
on PM sensor reading
IAQ prediction
support
Yes – LSTM model running
on ESP32 (edge).
ABSENT
ABSENT
ABSENT
Feature /
Aspect
Proposed Hybrid Edge-AI
Purifier (proposed system)
Dyson Purifier
(premium segment)
Philips Purifier (mid-
high segment)
Coway Purifier (value /
performance segment)
Fire detection
Dual layer Detection: Flame-
Array + Ai-Vision Verification
Detects
smoke/particles as
poor air quality but
not as fire; no flame
sensor.
Detects smoke/PM
as pollution; no fire-
specific logic.
Detects increased PM;
no explicit fire
detection.
Fan behaviour
during heavy
smoke / fire
Emergency logic cuts off fan
via relay within milliseconds,
triggers fire alert.
Auto mode likely
increases fan to clear
smoke; no
documented auto-
shutdown in fire.
Auto speed increases
with higher PM/gas;
no shutdown logic
for fire in manuals.
Fan speed increases for
higher PM; no special
fire-safe behaviour.
Emergency
shutdown
capability
Yes – The hardware interrupt
on flame makes fan OFF with
alarm.
No – It is not marketed
as fire safety system.
No – It is designed as
purifier and not fire-
safety device.
No – It is independent
of any fire detection.
Connectivity /
dependence on
cloud
Edge-only, runs without
internet; no cloud delay.
Wi-Fi, app, some
processing in cloud
ecosystem.
Wi-Fi + app; cloud
support for
monitoring and
control.
Offline with no
interaction features
User feedback /
interface
2.4 inchTFT display + Offline
Voice Interaction + Blynk
IoT.
Display, app graphs
colour indicators; no
voice alerts built-in
(only via assistant).
Panel indicators ,
app notifications;
colour ring for AQI.
Simple LEDs
indication
Maintenance /
filter life
indication
Planned: use runtime, PM
load estimate for filter alert
(prototype logic).
Filter-life indicator on
app.
Filter status
No logic or sensor
present.
Active Robotic
Response
Yes: Vision verification based
robotic Gimbal for Hazard
Scanning and verification.
No: Only stationary Air
filtration
No: Only stationary
Air filtration
No: Only stationary Air
filtration
Verification
Logic
Ai-Vision Verification
None:Not Present
None:Not Present
None:Not Present
Overall
uniqueness
Introducing a budget-
friendly innovation that fuses
Edge-based LSTM forecasting
with an automated Robotic
Vision Verification
framework. Distinct from
standard market purifiers,
this architecture
incorporates a localized
Voice Interface and Active
Fire-Mitigation capabilities,
delivering a multi-functional
safety and air-cleansing
solution within a unified,
microcontroller-driven
platform.
Highly featured
commercial purifier
with strong filtration
and smart comfort, but
no explicit fire-risk
shutdown.
Balanced consumer
purifier with solid
IAQ features and
app, but no edge
prediction or fire
integration
Very strong PM
cleaning performance
and value; minimal
smart features and no
fire logic.
Source: Prepared by the authors using information from official product specifications and manuals of Dyson, Philips,
and Coway air purifiers.
Dyson Air Treatment Products. Available at: https://www.dyson.in/air-treatment
Philips Air Purifiers. Available at: https://www.philips.co.in
Coway India Air Purifiers. Available at: https://cowayindia.in
PPS Thane. Comparison of Coway, Philips and Dyson Air Purifiers in India: https://www.ppsthane.com/blog/coway-
vs-philips-vs-dyson-air-purifier-india
7. Conclusion and future scope
Indoor air quality management and residential fire safety are two separate fields. Each has been handled by its
own passive system. This work shows that these areas can be effectively combined into a single, low-cost
embedded platform using a hybrid Edge-AI architecture. The proposed system addresses the oxygen fire
paradox, where a standard air purifier’s fan helps spread fire by circulating oxygenated air. It features a safety
mechanism that deactivates the relay through a deterministic hardware interrupt, achieving activation within
87 ms, regardless of the ongoing inference computation. The LSTM indoor air quality forecasting engine runs
entirely on the ESP32 using TensorFlow Lite for microcontrollers (TFLM), with an 8-bit quantized size of 142
KB. The predictive algorithm was trained using 4,400 valid one-minute samples (73.3 hours of real
environmental records) from the DALTON A1 dataset, split chronologically into 3,080 training (70%), 660
validation (15%), and 660 testing (15%) samples. The quantized on-device model achieved an insignificant
RMSE of 3.12 IAQ units (normalized error lower than 2.4% on 0-500 IAQ scale) and MAPE of 5.8%, proving the
mathematical and operational possibility of localized time series prediction on devices with restricted
resources. In a single representative test, the hardware-interrupt-based relay deactivation was measured at
approximately 87 ms; repeated trials to establish statistical variation are identified as necessary future
validation work. The vision verification layer uses a MobileNet V1-based SSD model running on the ESP32-CAM,
mounted on a servo assembly capable of a 360° horizontal and 180° vertical scan range. In preliminary testing
on a small, non-statistically-validated test set, the model reached an AUC-ROC of 0.91, which appeared sufficient
to distinguish actual fire signatures from common false-positive sources like incense sticks or candle heat; a
larger-scale evaluation with defined class counts and confidence intervals is identified as necessary future work.
This matters because a suppression system that activates unnecessarily is almost as problematic as one that
fails to activate - so the two-stage approach, where flame sensor data must be confirmed by visual inference
before any pump is triggered, adds a layer of reliability that purely sensor-driven designs simply cannot offer.
Filter degradation is handled differently here than in most consumer devices. Rather than alerting users after a
fixed number of operating hours, the system continuously estimates HEPA condition through measured
differential pressure across the filter membrane, while activated carbon health is tracked by integrating VOC
concentration against airflow over time. Both metrics feed into health indices that flag replacement need based
on actual loading, not calendar time. The VC-02 module ties this together on the user side - someone can simply
ask the device how the filter is doing, or what the current air quality is, and receive a spoken response in real
time. No phone, no app, no internet required. For elderly users or anyone unfamiliar with smart home
ecosystems, this is a meaningful practical difference. Taken together, the system moves the air purifier out of its
traditional role as a background appliance and into something closer to an active safety node in the home. The
cost of the full prototype falls between ₹8,000 and ₹10,000, which puts it well within reach of middle-income
households that cannot justify spending ₹25,000 or more on commercial alternatives offering far fewer safety
features. This affordability, combined with the offline-first design philosophy, makes the architecture
particularly relevant to dense urban settings in developing regions - environments that carry high pollution
exposure risk yet remain consistently underserved by the existing market. In that sense, the work speaks
directly to the goals laid out under UN SDG-3 on health and well-being, and SDG-11 on making cities safer and
more sustainable for all residents. Future work will focus on the implementation of ESP-NOW-based mesh
networking to develop a “whole-home safety mesh,” enabling the detection of hazardous gases by any single
unit in a building to trigger a coordinated shutdown of all connected units simultaneously. Additionally, further
investigation will explore alternative energy-harvesting methods, such as utilizing HEPA airflow to drive
microturbines for trickle-charging the backup battery system.
Acknowledgment
The authors would like to express their sincere gratitude to Dr. Amol Sankpal, Prof. Awij A.R. Alam and Prof.
Feroz Shaikh for their invaluable technical guidance and constant support throughout this research. We also
extend our thanks to M.H. Saboo Siddik College of Engineering (MHSSCE) for providing the necessary laboratory
facilities and resources. Finally, we appreciate the motivation and logistical assistance provided by our families
and friend Deepak Deshmukh during the prototype assembly phase.
CRediT Author Contribution Statement
Moinuddin Khan: Conceptualization, Formal analysis, Investigation, Methodology, Project administration,
Software, Validation, Writing – Original draft, Writing – Review & editing. Sadeem Khan: Investigation,
Resources, Writing – Review & editing. Saloni Kadam: Methodology, Resources, Writing – Review & editing.
Alfiya Ansari: Conceptualization, Investigation, Writing – Review & editing. Abdul Arham Malik: Investigation
and Writing – Review & editing. Amol Sankpal: Supervision. Feroz Shaikh: Supervision.
Funding Declaration
This research did not receive any specific grant from funding agencies in the public, commercial, or not-for-
profit sectors.
Data Availability Statement
The basic ecological time-series dataset used for the purpose of model training and evaluation is accessible on
an open-source basis via the DALTON repository. The model files of the trained TFLM quantized model and
evaluation scripts that support the study can be obtained from the corresponding author upon reasonable
request for academic purposes.
Conflict of Interest
There is no conflict of interest.
Artificial Intelligence (AI) Use Disclosure
During the preparation of this work, the authors used Gemini in order to find spelling mistakes, the language
and grammatical correctness of the manuscript. After using this service, the authors reviewed and edited the
content as needed and take full responsibility for the content of the publication.
Supporting Information
No Applicable.
References
[1]
X. Q. Lao, Challenges and Opportunities of Health Protection in the Twenty-First Century: Case Box 8.1
Case Study on Air Pollution: Air Pollution Is Destroying Our Health, Essentials for Health Protection:
Four Key Components, Oxford University Press, 2019, 206–206.
[2]
N. E. Klepeis, W. C. Nelson, W. R. Ott, J. P. Robinson, A. M. Tsang, P. Switzer, J. V. Behar, S. C. Hern, W. H.
Engelmann, The national human activity pattern survey (NHAPS): A resource for assessing exposure
to environmental pollutants, Journal of Exposure Science & Environmental Epidemiology, 2001, 11, 231–
252, doi: 10.1038/sj.jea.7500165.
[3]
L. Yang, W. Li, M. Ghandehari, G. Fortino, People-centric cognitive Internet of Things for the quantitative
analysis of environmental exposure, IEEE Internet of Things Journal, 2018, 5, 2353–2366, doi:
10.1109/JIOT.2018.2824551.
[4]
F. T. Lu, R. J. Laumbach, A. Legard, N. T. Myers, K. G. Black, P. Ohman-Strickland, S. Alimokhtari, A. de
Resende, L. Calderón, G. Mainelis, H. M. Kipen, Real-world effectiveness of portable air cleaners in
reducing home particulate matter concentrations, Aerosol and Air Quality Research, 2024, 24, 230202,
doi: 10.4209/aaqr.230202.
[5]
P. Kumar, A. B. Singh, T. Arora, S. Singh, R. Singh, Critical review on emerging health effects associated
with the indoor air quality and its sustainable management, Science of the Total Environment, 2023,
872, 162163, doi: 10.1016/j.scitotenv.2023.162163.
[6]
S. Vardoulakis, E. Giagloglou, S. Steinle, A. Davis, A. Sleeuwenhoek, K. S. Galea, K. Dixon, J. O. Crawford,
Indoor exposure to selected air pollutants in the home environment: A systematic review, International
Journal of Environmental Research and Public Health, 2020, 17, 8972, doi: 10.3390/ijerph17238972.
[7]
H. Chojer, P. T. B. S. Branco, F. G. Martins, S. I. V. Sousa, A novel low-cost sensors system for real-time
multipollutant indoor air quality monitoring-development and performance, Building and
Environment, 2024, 266, 112055, doi: 10.1016/j.buildenv.2024.112055.
[8]
G. Yu, G. Zhang, S. Poslad, Y. Fan, X. Xu, A study of quantifying the influence of kitchen human activity
on indoor air quality dynamics, Environmental Pollution, 2024, 362, 124900, doi:
10.1016/j.envpol.2024.124900.
[9]
F. Moldovan, L. Moldovan, Indoor air quality in an orthopedic hospital from romania, Toxics, 2024, 12,
815, doi: 10.3390/toxics12110815.
[10]
J. Saini, M. Dutta, G. Marques, Modeling indoor PM2.5 using Adaptive Dynamic Fuzzy Inference System
Tree (ADFIST) on Internet of Things-based sensor network data, Internet of Things, 2022, 20, 100628,
doi: 10.1016/j.iot.2022.100628.
[11]
P. Camacho-Magriñán, D. Sales-Lerida, A. Lara-Doña, D. Sanchez-Morillo, Leveraging low-cost sensor
data and predictive modelling for IOT-driven indoor air quality monitoring, Smart Cities, 2025, 8, 200,
doi: 10.3390/smartcities8060200.
[12]
L. Pang, C. Luo, W. Pan, Research on the impact of indoor control quality monitoring based on internet
of things, IEEE Access, 2023, 11, 139614-139627, doi: 10.1109/ACCESS.2023.3336706.
[13]
I. Talati, K. Shah, O. Patel, J. Tanna, A. Jain, A. D. Oza, A. A. Yadav, M. J. Alshayeb, M. A. Khan, S. Islam, Study
of AQI Monitoring System of Indoor Environment Using Machine Learning Model and IoT Device,
Rocznik Ochrona Środowiska, 2025, 27, 152–163, doi: 10.54740/ros.2025.013.
[14]
K. Rastogi, D. Lohani, Context-aware IoT-enabled framework to analyse and predict indoor air quality,
Intelligent Systems with Applications, 2022, 16, 200132, doi: 10.1016/j.iswa.2022.200132.
[15]
J. Saini, M. Dutta, G. Marques, Machine learning for indoor air quality assessment: a systematic review
and analysis, Environmental Modeling & Assessment, 2024, 30, 417–434, doi: 10.1007/s10666-024-
10001-1.
[16]
Y. Qian, J. Leng, K. Zhou, Y. Liu, How to measure and control indoor air quality based on intelligent
digital twin platforms: A case study in China, Building and Environment, 2024, 253, 111349, doi:
10.1016/j.buildenv.2024.111349.
[17]
M. Kim, T. Kim, S. Park, K. Lee, An indoor multi-environment sensor system based on intelligent edge
computing, Electronics, 2022, 12, 137, doi: 10.3390/electronics12010137.
[18]
G. Davrazos, G. Raftopoulos, T. Panagiotakopoulos, S. Kotsiantis, A. Kameas, Predictive Vigilance:
Harnessing Internet of Things and Machine Learning for Smoke Detection, 2024 15th International
Conference on Information, Intelligence, Systems & Applications (IISA), IEEE, 2024, 1–4, doi:
10.1109/IISA62523.2024.10786644.
[19]
R. N. Pietraru, A. Olteanu, M. Nicolae, R.-A. Crăciun, Contributions to the development of fire detection
and intervention capabilities using an indoor air quality IoT monitoring system, Sensors, 2025, 25,
6375, doi: 10.3390/s25206375
[20]
S. Abimannan, E.-S. M. El-Alfy, S. Hussain, Y.-S. Chang, S. Shukla, D. Satheesh, J. G. Breslin, towards
federated learning and multi-access edge computing for air quality monitoring: literature review and
assessment, Sustainability, 2023, 15, 13951, doi: 10.3390/su151813951.
[21]
S. Li, Review of engineering controls for indoor air quality: a systems design perspective, Sustainability,
2023, 15, 14232, doi: 10.3390/su151914232
[22]
Dyson Ltd., Dyson Air Treatment Products—Technical Specifications, Dyson India, 2025, [Online].
Available: https://www.dyson.in/air-treatment.
[23]
H. Yin, D. Jin, H. Hong, J. Moon, Y. H. Gu, IAQ-STL-ML: A novel indoor air quality prediction pipeline using
meta-learning framework with STL decomposition, Environmental Technology & Innovation, 2025, 38,
104107, doi: 10.1016/j.eti.2025.104107.
[24]
P. Karmakar, S. Pradhan, S. Chakraborty, Indoor air quality dataset with activities of daily living in low
to middle-income communities, Advances in Neural Information Processing Systems (NeurIPS), 2024,
70076-70100, doi: 10.52202/079017-2240.
Publisher Note: The views, statements, and data in all publications solely belong to the authors and
contributors. GR Scholastic is not responsible for any injury resulting from the ideas, methods, or products
mentioned. GR Scholastic remains neutral regarding jurisdictional claims in published maps and institutional
affiliations.
Open Access
This article is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License, which
permits the non-commercial use, sharing, adaptation, distribution and reproduction in any medium or format,
as long as appropriate credit to the original author(s) and the source is given by providing a link to the Creative
Commons License and changes need to be indicated if there are any. The images or other third-party material
in this article are included in the article's Creative Commons License, unless indicated otherwise in a credit line
to the material. If material is not included in the article's Creative Commons License and your intended use is
not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly
from the copyright holder. To view a copy of this License, visit: https://creativecommons.org/licenses/by-
nc/4.0/
© The Author(s) 2026